Description - RS232 to CAN Converters Module
Internet communications using TCP/IP is increasing in the industrial sector. Using Ethernet for network in industrial area is appealing because the required cabling is already installed. The CAN-Ethernet Gateway from ICP DAS is a solution that enables CAN networks to be coupled together over the Internet/Ethernet, whereby remote monitoring and control is possible. The CAN-Ethernet Gateway controls networked communication and makes a transparent CAN-based application interface available to the user.
The device supports a transparent, protocol-independent transfer of the CAN messages, thus allowing its implementation into a wide range of possible applications. Furthermore, the CAN-Ethernet Gateway can be used with various higher layer CAN protocols (e.g. CANopen, DeviceNet or other proprietary protocols). The following figure shows the application architecture for CAN-Ethernet Gateway .
Furthermore, i-7540D also can be used as Ethernet to CAN/RS-232/485 Device Server. The Device Server is an appliance that network enables any device with a serial communication port. By virtue of its independent operating system, protocol independence, small size and flexibility, Device servers are able to meet the demand of virtually any network-enable application. Most devices don't have network ports. i-7540D allows those devices to become connected to the network.
|
| |
Application
Control System
Monitor System
Building Automation
Factory Automation
Vehicle Automation
Home Automation |
Ordering information:
i-7540D
Internet communication controller with one CAN bus, one RS-232, one RS-485 and one Ethernet |
Features
80186-80 Embedded CPU, or compatible |
| Ethernet Protocols, TCP,UDP,IP,ICMP,ARP |
| 10/100 Base-TX Ethernet Controller |
| Reloadable Operating Software |
| Message transmitted by using TCP/IP protocol |
| Diagnostics |
| COM driver support interrupt & 1K QUEUE Input & Output buffer |
| Support one RS-232 port, one RS-485 port and one CAN port |
| 2500Vrms photo-isolation protection on CAN side. |
| Jumper select 120Ω terminator resistor for CAN channel |
| Phillip 82C 250/251CAN Transceiver |
| Support both CAN specification 2.0A and 2.0B. |
| Max transmission speed up to 1M bps for CAN and 115.2K bps for RS-232 & RS-485 |
| Max transmission distance of CAN over 1000m (follow CAN specification) |
| Built-in self-tuner ASIC controller on RS-485 port |
| 7-segment LED display. |
| Software configurable CAN and RS-232 communication parameters |
| Firmware updated from COM1 or Ethernet port |
| Support Web Configuration |
| Support max 25 Ethernet clients connection |
| Support for Virtual COM technology |
| Specifications |
| |
| CPU |
| CPU |
80186, 80MHz or compatible |
| SRAM |
512K Bytes |
| Flash |
512K Bytes |
| EEPROM |
16K Bytes |
| NVRAM |
31 Bytes (battery backup, data valid up to 10 year) |
| RTC (Real Time Clock) |
Yes |
| 64-bit Hardware Serial Number |
Yes |
| Built-in Watchdog Timer |
Yes |
| Communication Interface |
| COM1 |
RS-232 (TXD, RXD, RTS, CTS, GND) |
| COM2 |
RS-485 (D2+, D2-) |
| CAN |
One CAN port with two CAN bus connector interfaces (CAN_H, CAN_L) |
| Ethernet Port |
10/100Base-TX Ethernet Controller
(Auto-negotiating, Auto_MDIX, LED indicator) |
| COM Port Formats |
| Data bit |
7, 8 |
| Parity |
Even, Odd, None |
| Stop bit |
1 |
| Baud-rate |
115.2Kbps max. |
| CAN Port Formats |
| CAN Controller |
Phillip SJA1000T CAN Controller |
| CAN Transceiver |
Phillip 82C250 CAN Transceiver |
| Isolated |
2500Vrms on CAN side |
| Baud-rate |
1Mbps max. |
| Dimensions |
| i-7540D |
123 x 72 x 33 mm |
| Operating Environment |
| Operating Temperature |
-25°C to +75°C |
| Storage Temperature |
-40°C to +80°C |
| Power |
| Protection |
Power reverse polarity protection |
| Frame Ground for ESD Protection |
Yes |
| Required Supply Voltage |
+10 to +30VDC (non-regulated) |
|
Power consumption |
2.5W |
|